LV power cable

A low-voltage power cable is a type of power cable. It is suitable for fixed laying in AC 50Hz, rated voltage 3kv and below transmission and distribution lines for transmission of electric energy.

Category:

Purpose:

Scope of application of low-voltage power cable: buried in the soil or laid indoors, channels, tunnels, small insulation distance between lines, no pole tower, less land occupation, basically does not occupy the space on the ground.

Feature:

The possibility of electric shock is small and safe to use. It is less affected by climatic conditions and surrounding environment, with stable transmission performance and high reliability. The distributed capacitance is large, the maintenance workload is small, and it has more favorable conditions for the development of ultra-high voltage and large capacity, such as low temperature and superconducting power cables.

Detail

A low-voltage power cable is a type of power cable. It is suitable for fixed laying in AC 50Hz, rated voltage 3kv and below transmission and distribution lines for transmission of electric energy. The possibility of electric shock is small and safe to use. It is less affected by climatic conditions and surrounding environment, with stable transmission performance and high reliability. The distributed capacitance is large, the maintenance workload is small, and it has more favorable conditions for the development of ultra-high voltage and large capacity, such as low temperature and superconducting power cables. Scope of application of low-voltage power cables: buried in the soil or laid indoors, in trenches and tunnels, with small insulation distance between lines, no towers, less land, and basically no space on the ground.

Purpose

0.6/1kV cross-linked polyethylene insulated power cable

This product is suitable for power transmission and distribution in lines with an AC rated voltage of 0.6/1kV.

0.6/1kV cross-linked polyethylene insulated flame-retardant power cable

This product is suitable for power transmission and distribution in lines with an AC rated voltage of 0.6/1kV. Suitable for occasions that require flame retardancy.

0.6/1kV cross-linked polyethylene insulated low smoke, low halogen flame-retardant power cable

This product is suitable for power transmission and distribution in lines with an AC rated voltage of 0.6/1kV. Suitable for densely populated areas such as high-rise buildings and large shopping malls.

Model

0.6/1kV cross-linked polyethylene insulated power cable

Voltage level: 0.6/1kV

Model: YJV62、YJLV62、YJV63、YJLv63、YJV72YJLV72、YJV73、YJLV73、YJV72、YJLV72YJV73、YJLV73、YJV、YJLV、YJY、YJLYYJV22、YJLV22、YJV23、YJLV23、YJV32YJLV32、YJV33、YJLV33、 YJV42、YJLV42YJV43、YJLV43

Specification range (mm2): 1 core: 1.5-10002; 3. 4-core: 1.5~500; 5. 3+1, 3+2, 4+1 cores: 4-500;

Execution standard: GB/T12706-2008

0.6/1kV cross-linked polyethylene insulated flame-retardant power cable

Voltage level: 0.6/1kV

Model: Z-YJV62、Z-YJLV62、Z-YJV63、Z-YJLV63Z-YJV72Z-YJLV72、Z-YJV73、Z-YJLV73Z-YJV72、Z-YJLV72、Z-YJV73、Z-YJLV73Z-YJv、Z-YJLV、Z-YJV22、Z-YJLV22Z-YJV32、Z-YJLV32、Z-YJV42、Z-YJLV42

Specification range (mm2): 1 core: 1.5-10002, 3, 4 cores: 1.5-500; 5. 3+1, 3+2, 4+1 cores: 4-500;

Execution standards: GB/T19666-2005, GB/T12706-2008

0.6/1kV cross-linked polyethylene insulated low smoke, low halogen flame-retardant power cable

Voltage level: 0.6/1kV

Model: DDZA-YJV、DDZA-YJLV、DDZB-YJV、DDZB-YJLV、DDZC-YJV、DDZC-YJLV、DDZA-YJV22(62)、DDZA-YJLV22(62)、DDZB-YJV22(62)、DDZB-YJLV22(62)、DDZC-YJV22(62)、DDZC-YJLV22(62)、DDZA-YJV32(72)、DDZA-YJLV32(72)、DDZB-YJV32(72)、DDZB-YJLV32(72)、DDZC-YJV32(72)、DDZC-YJLV32(72)、DDZA-YJV42、DDZA-YJLV42 、DDZB-YJV42、DDZB-YJLV42、DDZC-YJV42、DDZC-YJLV42

Specification range (mm2): 1 core: 1.5-10002, 3, 4 cores: 1.5-500; 5. 3+1, 3+2, 4+1 cores: 4~500;

Execution standards: GB/T 19666-2005, GB/T 12706-2008

Usage characteristics

0.6/1kV cross-linked polyethylene insulated power cable

a、 The long-term allowable working temperature of cable conductors shall not exceed 90 ℃. During a short circuit (with a maximum duration of no more than 5 seconds), the maximum temperature of the cable conductor shall not exceed 250 ℃.

b、 The temperature environment during cable laying should not be lower than O ℃, and preheating should be carried out when it is lower than O ℃. The minimum bending radius of a 3-core cable without armor should not be less than 15 times the outer diameter of the cable, and for armored cables, it should not be less than 12 times the outer diameter of the cable. The minimum bending radius for single core unarmored cables shall not be less than 20 times the outer diameter of the cable, and for armored cables, it shall not be less than 15 times the outer diameter of the cable.

c、 The DC resistance of the cable shall comply with the provisions of GB/T3956-2008.

d、 Cable laying is not limited by horizontal drop.

e、 Power frequency withstand voltage test: Cables with U0 of 3.6kV and below: 2.5UO+2kV/5 minutes without breakdown.

0.6/1kV cross-linked polyethylene insulated flame-retardant power cable

a、 The long-term allowable working temperature of cable conductors shall not exceed 90 ℃. During a short circuit (with a maximum duration of no more than 5 seconds), the maximum temperature of the cable conductor shall not exceed 250 ℃.

b、 The temperature environment during cable laying should not be lower than 0 ℃, and preheating should be carried out when it is lower than O ℃. The minimum bending radius of a 3-core cable without armor should not be less than 15 times the outer diameter of the cable, and for armored cables, it should not be less than 12 times the outer diameter of the cable. The minimum bending radius for single core unarmored cables shall not be less than 20 times the outer diameter of the cable, and for armored cables, it shall not be less than 15 times the outer diameter of the cable.

c、 The DC resistance of the cable shall comply with the provisions of GB/T3956-2008.

d、 Cable laying is not limited by horizontal drop.

e、 Power frequency withstand voltage test: Cables with U0 of 3.6kV and below: 2.5UO+2kV/5min without breakdown.

f、 Flame retardant properties: Flame retardant cables can withstand the bundled combustion test specified in GB/T18380.3-2001.

0.6/1kV cross-linked polyethylene insulated low smoke, low halogen flame-retardant power cable

a、 The long-term allowable working temperature of cable conductors shall not exceed 90 ℃. During a short circuit (with a maximum duration of no more than 5 seconds), the maximum temperature of the cable conductor shall not exceed 250 ℃.

b、 The temperature environment during cable laying should not be lower than O ℃, and preheating should be carried out when it is lower than O ℃. The minimum bending radius of a 3-core cable without armor should not be less than 15 times the outer diameter of the cable, and for armored cables, it should not be less than 12 times the outer diameter of the cable. The minimum bending radius for single core unarmored cables shall not be less than 20 times the outer diameter of the cable, and for armored cables, it shall not be less than 15 times the outer diameter of the cable.

c、 The DC resistance of the cable shall comply with the provisions of GB/T3956-2008.

d、 Cable laying is not limited by horizontal drop.

e、 Power frequency withstand voltage test: Cables with U0 of 3.6kV and below: 2.5UO+2kV/5 minutes without breakdown.

f、 Can withstand the bundled combustion test specified in GB/T18380.3-2001, and the smoke concentration during combustion should comply with GB/T19666-2005.

Keywords:

Other Products

Rubber Sheathed Cable

Mobile flexible cable is mainly by the rubber insulation rubber (or similar material) sheath, the fifth or sixth kind of conductor structure of the cable.

MYPTJ

The conductor of the flexible rubber‑sheathed mobile mining cable typically consists of several strands of fine copper wires. The insulation material is an ethylene‑propylene rubber compound, while the sheath material is a flame‑retardant chlorinated polyethylene blend. Different shielding structures and sheath colors are employed depending on the voltage levels. This cable is primarily used for electrical connections in underground mobile mining equipment, for connecting cutting machines and similar devices, for linking underground frequency‑conversion units, as well as for interfacing with mobile frequency converters installed underground, among other applications. The conductor of the flexible rubber‑sheathed mobile mining cable typically consists of several strands of fine copper wires. The insulation material is an ethylene‑propylene rubber compound, while the sheath material is a flame‑retardant chlorinated polyethylene blend. Different shielding structures and sheath colors are employed depending on the voltage levels. Purpose >>Mobile rubber-sheathed flexible cable for coal minesPower connection of mobile coal mining equipment both above and below the mine shaftThe mobile shielded rubber sheathed flexible cable used in coal mines is used for power connection of mobile coal mining equipment both above and below the mine shaft.Mobile metal-shielded rubber-sheathed flexible cable for coal minesPower connection for mobile coal mining equipment in and under the mineMobile metal-shielded monitoring rubber-sheathed flexible cable for coal minesPower connection of mobile coal mining equipment both above and below the mine shaftPower connection of rubber-sheathed cables for electric drills used in coal mines, connecting mobile coal mining equipment both above and below the mine shaftMobile light rubber-sheathed flexible cable for coal minesPower connection of mobile coal mining equipment in and under the wellRubber-sheathed flexible cable for coal cutterPower connection for coal cutters and similar equipment with rated voltage of 0.38/0.66kVCoal cutter shielded rubber sheathed flexible cablePower connection of coal cutters and similar equipmentMetal-shielded rubber-sheathed flexible cable for coal cuttersPower connection for coal miners and similar equipment.Coal mine electric drill shielded rubber-sheathed cableShenzhou CableLighting for underground coal mine tunnels, interlocking of conveyors, and power connection for control and signaling equipment Model and specification >>Mobile rubber-sheathed flexible cable for coal minesmodelspecificationMY1 core: 4~1853+1 core power cable, core size 4~185; grounding core size 4~50execution standardMT 818.5-2009Mobile shielded rubber sheathed flexible cable for coal minesmodelspecificationexecution standardMYPMYP 0.38/10.66kV, 0.66/1.14kV: 3+1 cores: power core 4~185; ground core 4~50 MYP 3.6/6kV: 3+1 cores: power core 16~150; ground core 16~50MT818.5-2009MT818.7-2009Mobile metal-shielded rubber-sheathed flexible cable for coal minesmodelspecificationMYPTMYPT 1.9/3.3kV:3+1 core: power core 35~150; ground core 35/3~50/3, Shenzhou Shenlan MYPT 3.6/6kV, 6/10kV:3+1 core: power line core 16~150; ground wire core 35/3~50/3execution standardMT818.7-2009Mobile metal-shielded monitoring rubber-sheathed flexible cable for coal minesmodelspecificationexecution standardMYPTJMYPTJ3.6/6kV3+3+3 cores: power core 25~150; ground core 35/3~50/3; monitoring core: 2.5MYPTJ6/10kV. 8.7/10kV:3+3+3 cores: power line core 25~185; ground wire core 35/3~50/3; monitoring line core: 2.5MT 818.7-2009Rubber-sheathed cable for electric drills used in coal minesmodelspecificationexecution standardMZ3+1 cores, 3+1+1 cores: power core 2.5~4; ground core 2.5~4MT 818.8-2009Mobile light rubber-sheathed flexible cable for coal minesmodelspecificationexecution standardMYQ2, 3, 4, 7, 12 cores: 1~2.5MT &18 8-2009Rubber-sheathed flexible cable for coal mining machinemodelspecificationexecution standardMC3+1 core: power core 16~120: ground core 4~25MT 818.2-2009Sheath shielding flexible cable for coal mining machinemodelspecificationexecution standardMCPMCP_0.38/0.66kV• 3+1 core. Power core 16~120: Ground core 4~25MCP-0.66/1.14kV MCP-1.9/3.3kV: 3+1 cores: power core 16~150;Ground wire core 4~35MT 818.2-2009modelspecificationexecution standardMetal-shielded rubber-sheathed flexible cable for coal mining machinesMCPT, MCPTJMCPT (MCPTJ)-0.66/1.14kV: 3+1+1 cores: power core 4~185;Ground wire core 4~70: Control wire core: 1.5~10MCPT-(MCPTJ)1.9/3.3kV: 3+1+1 core: power core 16~150;Ground wire core: 16~70; Control wire core: 2.5~10MT 818.4-2009modelspecificationexecution standardShielded rubber-sheathed cable for electric drills in coal minesMZP3+1 core, 3+1+1 core: power core 2.5~4; ground core 2.5~4MT 818.8-2009 Usage characteristics• Mobile rubber-sheathed flexible cable for coal minesRated voltage: 0.38/0.66kV; the minimum bending radius of the cable is 6 times the cable diameter; the ground wire should be well g

MYJV22

It is primarily used for the electrical connection of underground mobile mining equipment, for connecting shearer cables and similar devices, for interfacing underground frequency converters, and for connecting mobile frequency converters installed underground.The conductors of mining power cables typically consist of multiple strands of thick copper wires; the insulation material is an ethylene‑propylene rubber compound, while the jacket is made from a flame‑retardant chlorinated polyethylene blend. Furthermore, shielding structures and jacket colors are selected according to voltage levels.Purpose>Polyvinyl chloride insulated power cable for coal mines with rated voltage of 1.8/3kV and belowThis product is a fixed-laying cable for coal mines with a rated voltage of 1KV and below, suitable for power transmission in coal mine shaftsCoal mine-used XLPE insulated power cable with rated voltage of 8.7/10 kV and belowThe wooden product is a fixed-laying cable with a rated voltage of 10KV or below for use in coal mines, specifically for power transmission underground.Model and specificationPVC insulated power cable for coal mines with rated voltage of 1.8/3kV and belowmodelSpecification range (mmz)execution standardMVV. MVV22. MVV32. MVV420.6/1kVMVV. MVV223, 3+1#: 4~300 ;0.6/1 kV MVV, MVV224t: 4~185 ;1.8/3KV MVV. MVV223, 3+1€: 10 ~ 3001.8/3kV MVV. MVV224t: 10 ~ 185 ;MT 818.11-2009. MT 818.12-2009》Cross-linked polyethylene insulated power cables for coal mines with rated voltage of 8.7/10kV and belowmodelSpecification range (mm2)Implement standardsMYJV. MYJV22, MYJV32, MYJV420.6/1kVMYJV. MYJV223, 3+1: 4~3000.6/1kV MYJV. MYJV22 4t: 4~ 185 :0.6/1kV MYJV32, MYJV423+1: 4~300 :0.6/1kV. 1.8/3kV MYJV323t: 16 ~ 300 :0.6/1kV -• 1.8/3kV MYJV423: 50 ~ 3001.8/3KV MYJV. MYJV22 3, 3+1#: 10 ~ 300 ;1.8/3KV MYJV. MYJV224: 10 ~ 185 ;1.8/3kV MYJV32. MYJV42 3+1#: 10 ~ 300 :3.6/6, 6/6, 8.7/10kV MYJV, MYJV22,MYJV32 • 25 ~ 300. MYJV42 • 50 ~ 300MT 818.11-2009, MT 818.12-2009Usage characteristics• PVC insulated power cables for coal mines with rated voltages of 1.8/3kV and belowRated voltage: 0.6/1kV, 1.8/3kVThe maximum rated operating temperature of the cable conductor is 70°C.During a short circuit (with a maximum duration of no more than 5 seconds), the maximum temperature of the cable conductor does not exceed 160°CThe ambient temperature during cable laying should not be lower than 0°C, and the minimum bending radius should be 15 times the diameter of the cable.• Cross-linked polyethylene insulated power cables for coal mines with rated voltages of 8.7/10kV and belowRated voltage: 0.6/1kV, 1.8/3 kV, 3.6/16kV, 6/10kV, 8.7/10kVThe maximum rated operating temperature of the cable conductor is 90°C.During a short circuit (with a maximum duration not exceeding 5 seconds), the maximum temperature of the cable conductor does not exceed 250°C.The ambient temperature during cable laying should not be lower than 0°C, and the minimum bending radius should be 15 times the diameter of the cable Cable structure diagram1. Conductor2. Insulating layer3. Filling4. Sheath5. Inner lining layer6. Armor 

BTTZ

Flexible mineral insulated cable is composed of copper core, metal sheath and magnesium oxide insulation and other inorganic materials, the main models are BTTQ, BTTVQ, BTTYQ, BTTZ, BTTVZ BTTVZ.

BTTVZ

Flexible mineral insulated cable is composed of copper core, metal sheath and magnesium oxide insulation and other inorganic materials, the main models are BTTQ, BTTVQ, BTTYQ, BTTZ, BTTVZ BTTVZ.

BBTRZ

Flexible mineral insulated cable is composed of copper core, metal sheath and magnesium oxide insulation and other inorganic materials, the main models are BTTQ, BTTVQ, BTTYQ, BTTZ, BTTVZ BTTVZ.

BTLY(NG-A)

Flexible mineral insulated cable is composed of copper core, metal sheath and magnesium oxide insulation and other inorganic materials, the main models are BTTQ, BTTVQ, BTTYQ, BTTZ, BTTVZ BTTVZ.

Overhead conductor

Overhead lines mainly refer to overhead open lines, which are erected above the ground and are transmission lines that use insulators to fix transmission conductors on towers standing on the ground to transmit electrical energy.

Home improvement BV wire

The insulation layer is made of materials that comply with the EU RoHS environmental protection directive, with good flame retardant performance and no toxic substances. The conductor is made of 99.99 oxygen-free copper with lower resistance, higher conductivity, low carbon and energy saving, and long service life.

YJHLV22-(YJLHV22)-Rare earth high iron steel tape armored aluminum alloy cable

The conductor is made of aluminum alloy AA8030 high conductive alloy conductor, which has high creep resistance, high flexibility, high elongation, increased tensile strength, and safe and stable connection. The armor layer uses high-strength double steel tape armor, which can withstand greater pressure. The sheath is made of environmentally friendly anti-radiation PVC, which has good corrosion resistance and a wider range of use.

ZB-ACWU90(-40)-(YJLHVS2)-Interlocking armored aluminum alloy cable

Is a highly flexible interlocking aluminum alloy armor, PVC outer sheath, 90 ℃ cross-linked polyethylene waterproof insulation single-core or multi-core cable, and does not contain heavy metal elements, green environmental protection.

ZA-AC90(-40)-(YJLHS)-Interlocking armored non-sheathed aluminum alloy cable

Armored cable is a highly flexible self-locking alloy armored, 90 degree cross-linked polyethylene insulated single-core or multi-core low-smoke halogen-free flame-retardant Class A cable.

I want to consult

Your consultation will help us provide you with the most accurate quotation information

Submit

*Please fill in the above fields (fields marked with an asterisk are required), and we will reply to your feedback as soon as possible.

Get a Quote

Your consultation will help us provide you with the most accurate quotation information

Submit

*Please fill in the above fields (fields marked with an asterisk are required), and we will reply to your feedback as soon as possible.